OUR OFFICE
Rukan Great Wall, Jl. Green Lake City Boulevard No.63 Blok B, RT.002/RW.008, Petir, Kec. Cipondoh, Kota Tangerang, Banten 15146 Indonesia
Want to learn more?
Contact UsA manufacturing facility relies on gas to operate its boilers, ovens, burners, and process-heating equipment. Production volumes remain relatively stable, yet recorded gas consumption continues to rise. The operations team begins reviewing burner performance. Finance examines supplier invoices. Meanwhile, the engineering team has limited information about when the additional consumption occurred.
Is the increase caused by longer operating hours, changes in process efficiency, or differences between the volume displayed by the gas meter and the volume used for billing? Higher industrial gas consumption does not necessarily mean energy is being wasted. Before reaching that conclusion, companies need to understand production activity, measurement conditions, and how the gas is used.
Internet of Things (IoT) monitoring can help by collecting consumption readings more frequently and making historical information available to operational teams. However, interpreting that data correctly requires an understanding of gas measurement.
Gas fuels various industrial processes requiring thermal energy. In food manufacturing, it may be used for ovens, cooking equipment, dryers, and steam generation. Other industries rely on gas-fired furnaces, boilers, and process heaters.
Consumption depends on production demand, operating schedules, equipment performance, and the characteristics of the fuel and process. Several causes should be considered before attributing an increase to inefficiency.
A process that operates longer will generally require additional energy. For example, an oven running for ten hours may consume more gas than the same oven operating for six hours, even when combustion performance has not changed. Product specifications also matter, different products may require different heating temperatures, processing durations, or thermal loads.
For meaningful comparisons, total gas consumption should be evaluated alongside production volume, operating hours, processed material, or another suitable output measure. Without such context, higher consumption is not sufficient evidence of declining energy efficiency.
The condition of process-heating equipment can influence gas use. Inappropriate burner settings, reduced heat-transfer performance, and maintenance issues may increase fuel requirements for a given process.
The US Department of Energy's industrial energy resources emphasize system-level assessments, maintenance, and operating improvements for combustion and process-heating systems. However, a rise in metered consumption does not independently establish that a burner is faulty.
Engineers may need additional information, including operating temperatures, combustion analysis, process conditions, and equipment status. Combustion equipment inspection and adjustment should be performed by qualified personnel under appropriate safety procedures.
Industrial facilities often have changing shift schedules and production demand. A boiler or heating system may continue operating at a particular setting even when process demand has fallen.
This does not automatically mean the equipment is being operated inefficiently. Some systems require thermal readiness or have legitimate standby requirements. Nevertheless, comparing gas consumption against operating schedules can reveal conditions that deserve investigation.
Another source of confusion is the difference between measured gas volume and the volume used for reporting or billing. Natural gas volume changes with pressure and temperature. Consequently, measurements at operating conditions may need to be converted to agreed reference conditions before meaningful comparisons are made.
For natural gas metering, pressure and temperature are fundamental considerations. Unlike liquids under typical operating conditions, gases are readily compressible. The volume occupied by a given amount of gas can therefore vary considerably with operating conditions.
Certain volumetric gas meters measure gas passing through the instrument under prevailing pressure and temperature conditions. This is often described as the operating or actual volume. A change in pressure can change the measured volume associated with the same quantity of gas.
Comparing operating volumes from different conditions without accounting for those differences may therefore be misleading.
For consistent reporting, measured volumes may be converted to defined reference conditions. ISO 13443 specifies standard reference conditions used in natural gas measurement and calculations. ISO 15970 addresses the measurement of properties relevant to volume conversion, including pressure, temperature, density, and compressibility.
Terms such as m³, Nm³, and Sm³ may appear in gas measurement systems. These labels should be interpreted alongside the applicable reference conditions and contractual definitions. A value described as normalized or standard volume should not be compared directly with another unless the reference basis is consistent.
An Electronic Volume Corrector (EVC) converts gas volume measured under operating conditions to a defined reference basis. Depending on the system, it receives meter volume information and pressure and temperature measurements.
The correction may also incorporate gas compressibility according to the applicable calculation method. OIML R 140 addresses correction and conversion functions within gaseous fuel measurement systems. Commercial devices such as Honeywell's EC250 provide pressure, temperature, and compressibility-based correction for supported gas-metering applications.
Not every installation requires the same type of volume corrector. Equipment selection depends on meter technology, operating conditions, measurement requirements, and applicable commercial or regulatory arrangements. The principles discussed here primarily concern natural gas. LPG installations may use different measurement, storage, delivery, and billing arrangements. Mass-based LPG consumption in kilograms, for example, should not be treated as directly equivalent to a natural-gas volume reading.
A monthly meter reading establishes accumulated consumption over a billing period. It does not identify precisely when demand increased. More frequent readings can provide information about gas usage during individual shifts, production periods, or operating schedules.
For example, a facility may discover that consumption remains high during periods when production equipment should be operating at reduced demand. That information can support a targeted investigation. However, scheduled cumulative readings do not necessarily provide continuous instantaneous flow measurements. An hourly consumption value calculated from two cumulative readings represents average consumption over that interval, not every variation that occurred within it.
An IoT monitoring system connects compatible gas-metering equipment to a communication network and monitoring application. Depending on the meter, readings may be obtained through pulse outputs, digital interfaces, or supported industrial protocols. A gateway or communication device transfers the information to a central platform.
The dashboard may display cumulative consumption, interval usage, historical patterns, and device status. Pressure, temperature, and corrected-volume information may also be available when appropriate instruments and interfaces are integrated.
| Component | Function | Monitoring Value |
|---|---|---|
| Gas Meter | Measures gas volume at the metering point. | Provides consumption records. |
| Electronic Volume Corrector | Converts measured volume to reference conditions. | Supports consistent volume comparison. |
| Pressure Sensor | Measures gas pressure at an appropriate point. | Supports volume correction and analysis. |
| Temperature Sensor | Measures gas temperature. | Provides information about measurement conditions. |
| IoT Gateway | Transfers instrument data through a communication network. | Enables remote data collection. |
| Monitoring Dashboard | Displays historical measurements and device status. | Supports time-based consumption analysis. |
Compatible gas meters can be connected through pulse-reading devices or digital communication interfaces. For pulse-based systems, the software must use the correct volume-per-pulse factor.
An incorrect factor can create substantial measurement discrepancies. Commissioning should therefore include configuration checks and comparison between digital readings and the physical meter register.
A facility may distribute gas to several production lines. Installing suitable measurement points can help operators understand how consumption is distributed across processes. Main-meter readings can be compared with data collected from individual areas, provided the measurement basis and time periods are aligned.
Any differences require further examination of meter accuracy, network boundaries, process conditions, and measurement timing. The purpose of additional monitoring is to improve the information available for diagnosis, not to claim that every discrepancy represents leakage.
Historical data allows teams to compare expected and observed consumption patterns. Applications may support configurable alerts for unexpected usage, missing readings, or equipment status changes.
However, abnormal consumption should not automatically be classified as a gas leak. Changes in production, burner operation, and process schedules may create similar patterns.
Where a hazardous gas release is suspected, the facility must follow approved safety procedures and use appropriate gas detection and protection systems. Consumption monitoring dashboards are not substitutes for gas detectors, emergency shutdown systems, or safety-critical controls.
Total gas consumption shows how much fuel was used over a period. It does not, by itself, establish how efficiently the fuel contributed to production. A more useful measure may be consumption per unit of output. Consider a hypothetical production process using 1,200 m³ of gas, measured on a consistent basis, to manufacture 12,000 product units.
Specific consumption would be:
1,200 m³ ÷ 12,000 units = 0.10 m³ per product unit
If the same production volume later required 1,350 m³, specific consumption would increase to 0.1125 m³ per unit. This represents a 12.5% increase in specific gas consumption.
The example is illustrative and does not represent a verified IKI installation. Before concluding that efficiency has declined, the company should evaluate changes in product mix, raw materials, operating conditions, and the gas measurement basis. If the goal is to compare thermal energy efficiency, the fuel's applicable calorific value should also be considered.
IoT monitoring does not always require replacing the existing gas meter. Some installed instruments provide pulse outputs or communication interfaces that can support external monitoring. Compatibility must be verified for the specific meter model.
A preliminary assessment should identify the fuel type, meter specifications, operating pressure, correction requirements, available interfaces, and desired reporting frequency. The facility should also assess communication coverage, power availability, installation conditions, and applicable safety requirements.
Installation of additional instruments or modifications to gas infrastructure must be performed under appropriate technical and safety authorization. Once integration is completed, digital readings should be validated against available reference information and the existing measurement system.
PT IoT Kreasi Indonesia (IKI) provides Internet of Things devices, connectivity infrastructure, monitoring applications, and system integration services.
IKI's official website includes a Smart Gas Meter product portfolio for gas-consumption measurement applications within the stated equipment specifications.
Industrial monitoring systems may be designed around compatible existing instruments or additional metering equipment, depending on the project. Available data can include volume readings, historical consumption, and other supported measurement parameters.
Meter capacity, volume-correction requirements, communication interfaces, and installation safety must be evaluated before deployment. IoT monitoring supports operational visibility. It does not replace metrological verification, technical inspection, or industrial gas safety procedures.
Possible causes include operating schedules, heating equipment performance, process conditions, and differences in measurement or reporting. Historical consumption and production data are needed to identify the underlying cause.
Some meters support pulse outputs or digital communication interfaces. Integration depends on the meter model, specifications, and available communication equipment.
An m³ reading may refer to volume at specified operating conditions, while Nm³ generally refers to volume expressed at defined reference conditions. The reference definition must be checked because conventions may differ.
No. The requirement depends on the measurement method, operating conditions, equipment, and applicable reporting or commercial requirements.
Unexpected consumption may justify further investigation, but consumption data alone cannot reliably establish a hazardous gas leak. Appropriate gas detection systems and safety procedures remain necessary.
No. Connectivity may use LoRaWAN, cellular networks, Ethernet, or another supported interface depending on application requirements.
Rising industrial gas consumption should prompt investigation, not an automatic conclusion that fuel is being wasted. Production activity, equipment operation, measurement conditions, and the distinction between actual and corrected volume all influence how gas data should be interpreted.
IoT monitoring makes consumption history more accessible and can help operational teams identify changes that deserve attention. Its value depends on suitable instruments, correct configuration, reliable communication, and meaningful action after the data is reviewed. Organizations evaluating industrial gas-meter integration can explore PT IoT Kreasi Indonesia for information about connected metering and IoT system integration.
International Organization for Standardization. (1996, confirmed in 2025). ISO 13443:1996 — Natural Gas, Standard Reference Conditions. https://www.iso.org/standard/20461.html
International Organization for Standardization. (2008). ISO 15970:2008 — Natural Gas, Measurement of Volumetric Properties. https://www.iso.org/standard/44868.html
International Organization of Legal Metrology. (2007). OIML R 140 — Measuring Systems for Gaseous Fuel. https://www.oiml.org/en/files/pdf_r/r140-e07.pdf/%40%40download/file/R140-e07.pdf
US Department of Energy. (2020). Energy Intensity Baselining and Tracking Guidance. https://betterbuildingssolutioncenter.energy.gov/sites/default/files/attachments/Energy%20Intensity%20Baselining%20and%20Tracking%20Guidance%202020.pdf
US Department of Energy. Steam Systems. https://www.energy.gov/cmei/ito/steam-systems
Honeywell. EC250 Volume Corrector. Official product documentation. https://process.honeywell.com/us/en/products/gas/distribution/volume-converters/ec250-volume-corrector
PT IoT Kreasi Indonesia. Smart Gas Meter. https://www.weiots.io/product/smart-meter/smart-gas-meter